Specifications
Environmental RatingIP65 (NEMA 4X)
Air Consumption0.04 SCFM steady state average (0.06 SCFM maximum)
Certifications/ComplianceCE marked, ATEX, CSA/US
ConnectionsSupply port; 0.25 in. NPTF (1X); Pneumatic Output Port: 0.25 in. NPTF (2X); Electrical: 0.5 in. NPTF conduit (2X); terminals 12 to 22 AWG wire
Deadband0.02% of span
DescriptionSTD5000 and STD6000 Current-to-Pressure (I/P) Transducers
Enclosure MaterialCast Aluminum with Powder-coated Epoxy
Failure ModeMechanically direct (i.e., if the input current drops below 3.7mA DC, the output will drop to 1 to 2psig regardless of direct or reverse mode selection)
Frequency Response-3 dB at 5 Hz (per ISA-S26.4.3.1 Configuration A)
Loop Load3.8 VDC + 5 ohm (19 5ohm load at 20 mA)
Operating ModesField selectable direct, reverse and/or split range; see notes in model number description
OutputsStandard: 4.0 SCFM (supply and exhaust characteristics are balanced to within ±10%); High Pressure: 4 to 8 SCFM possible (dependent on air supply and tubing size)
Repeatability0.05% of span
Stability0.5% of span/6 months
Vibration Effect<0.25% from 1 to 200Hz/1g
Weight (English)2.5 lb.
Weight (Metric)1.13 kg
Unit SizeEach